Residual Current Operated Circuit Breaker with Over-current Protection
Basic Info
Model No.: 112
Product Description
1. Application
TFDZ47LE is applicable to a line of AC 50Hz/60Hz, rated voltage 230V for single pole two-wire, 2-pole or 400V for 3-pole, 3-pole 4-wire, and 4-pole and rated current up to 40A. It can protect the line and motor from overload and short circuit. It can also be used for infrequent line conversion and infrequent motor start. It conforms to the standards of IEC61009
2. The over-current protection property
Ambient | Initial Status | Test | Expected Result | Expected Result | Note |
30±2℃ | Cold position | 1.13In | t≥1h | Non-release | -- |
Carried out immediately after | 1.45In | t<1h | Release | -- | |
previous test | Release | ||||
Cold position | 2.55In | 1s<t<60s | Release | Current smoothly rises to specified | |
Cold position | 2.55In | 1s<t<120s | Release | ||
-5 - +40℃ | Cold position | 3In | t≥0.1s | Non-release | Type B |
Cold position | 5In | t≥0.1s | Release | Type B | |
Cold position | 5In | t≥0.1s | Non-release | Type C | |
Cold position | 10In | t≥0.1s | Release | Type C | |
Cold position | 10In | t≥0.1s | Non-release | Type D | |
Cold position | 20In | t≥0.1s | Release | Type D |